■ On-line monitoring function: (SAT-AG A type series is without this function)
when the battery pack is under the state of online discharge, uniform charge and floating charge, perform real-time online monitoring for all cells. The monitoring items include pack voltage, cell voltage, charge/discharge current, monitoring time of battery pack, charge/discharge capacity of battery pack and etc.
The user can also monitor the temperature of each cell, so that it is better to control the situation of each cell. (optional function)
■ Discharge function:
Perform discharge of constant current taking advantage of intellectualized dummy load after the battery pack is removed from system, set up the parameters of “discharge current”, “discharge time ”, “discharge capacity” , “final
protective voltage of whole pack” and“ final protective voltage of cell”, and the tester could carry out discharge
function automatically, display discharge current, battery discharged capacity, the whole pack voltage, cell voltage,
discharge time and etc; when the pack reaches setup value of final discharge voltage, setup value of final discharge
capacity, setup value of final discharge time, any cell voltage which is below setup value of final cell voltage or manual final operation could stop discharge test.